Aluminum stranded conductor and steel core aluminum stranded conductor

Home >> Products >> Details
Aluminum stranded conductor and steel core aluminum stranded conductor
Usage:
The cable is manufactured according to GB12706-91 or IEC60502. It is suitable to be installed in the four wires system with rated voltage of 0.6/1KV (Uo/U) for transmitting electricity
Standards:
The maximum operating temperature of cores shall not exceed 70℃when the cable is used for long period. The temperature of cores shall not exceed 160℃at short circuit for 5 seconds .The ambient temperature should not be below 0℃during installation. The minimum-bending radius shall not be less than 10 times of the cable diameter when lying. The single cable should not be laid in magnetic ducts when it is electrified with alternating current.
Operating characteristics:
Cores number: (1~5) cores   Nominal cross-sectional area: (1.5~630mm2)
All sorts of this products include:
Name:Aluminum stranded conductor Nominal cross-sectional:35,25,16
Size:
Model:LJ35,LJ25,LJ16
Rated voltage:   Dark Fiber: Use:
 Parameter
Nominal cross-sectional area
Conductor's
structure wire
number/single wire
diameter
Calculation outer diameter
Max.dc,resistance at 20℃
Calculated breaking load
Reference weight

Delivery length

Continuous carrying capacity
16
7/1.70
5.10
1.8020
2840
43
4000
111
25
7/2.15
6.45
1.1270
4355
69.6
3000
147
35
7/2.50
7.50
0.8332
5760
94.1
2000
180
50
7/3.00
9.00
0.5786
7930
135.5
1500
227
70
7/3.60
10.80
0.4018
10590
195.1
1250
284
95
7/4.16
12.48
0.3009
1445
260.5
1000
338
120
19/2.85
14.25
0.2373
19420
333.5
1500
390
150
19/3.15
15.75
0.1943
23310
407.4
1250
454
185
19/3.50
17.50
0.1574
28440
503.0
1000
518
210
19/3.75
18.75
0.1371
32260
577.4
1000
575
240
19/4.00
20.00
0.1205
36260
656.9
1000
610
300
37/3.20
22.40
0.09689
46850
820.4
1000
707
400
37/3.70
25.90
0.07247
61150
1097.0
1000
851
500
37/4.16
29.12
0.05733
76370
1387.0
1000
982
630
61/3.63
32.67
0.04577
91940
1744.0
800
1140
800
61/4.10
36.90
0.3588
115900
2225.0
800
1340